Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 22, 2019, 11:00 AM
  • Section#10_15 0816_15 0815__1222019__I0097.mp4

Date
01/22/2019
W/O
0749485
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P13017
Time
3:00 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0097
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
ARCADIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190118MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
9.420000076293945 in.
Upstream MH
15 0816
Downstream MH
15 0815
Dir. of Survey
Downstream
Length Surveyed
358.9 ft.
Total Length
358.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3312
O&M Rating
11
Overall Index
2
Overall Quick
Overall Rating
11
Pipe schematic from manhole 15 0816 to 15 0815
MH: 15 0816MH: 15 0815downstream0 ft. MGO - General Observation - ACTIVE MH CONN 3:000 ft. MGO - General Observation - STUB MH CONN 9:000 ft. AMH - Upstream Manhole, Survey Begins - 4:10AM17.5 ft. MGO - General Observation - 9.4" NRCP + CIPP LINER43.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN47.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN72.5 ft. RFL - Roots Fine Lateral, at 10 o'clock - 2%72.5 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - ACTIVE- 50% ROOTS150.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.8 ft. MGO - General Observation - CIPP LINER226.2 ft. RFL - Roots Fine Lateral, from 08 to 10 o'clock - 3%226.2 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN- 30% ROOTS228.8 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN- 50% ROOTS358.3 ft. MGO - General Observation - STUB MH CONN 9:00358.3 ft. MGO - General Observation - STUB MH CONN 3:00358.9 ft. AMH - Downstream Manhole, Survey Ends - 4:35AM

Observation photos (2)

  • General Observation - 9.4" NRCP + CIPP LINER

    17.5 ft. - General Observation - 9.4" NRCP + CIPP LINER

  • General Observation - CIPP LINER

    211.8 ft. - General Observation - CIPP LINER

Observations (16)

DistanceCodeObservation
211.8MGOCIPP LINER
358.9AMH4:35AM
0MGOACTIVE MH CONN 3:00
72.5RFL2%
17.5MGO9.4" NRCP + CIPP LINER
43.4TBOPEN
0MGOSTUB MH CONN 9:00
226.2RFL3%
150.9TBOPEN
72.5TBDACTIVE- 50% ROOTS
47.3TBOPEN
358.3MGOSTUB MH CONN 9:00
228.8TBDOPEN- 50% ROOTS
358.3MGOSTUB MH CONN 3:00
0AMH4:10AM
226.2TBDOPEN- 30% ROOTS

Properties (5)

custom_field_three
CIPP LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-22T03:00:37-08:00
lining
CIPP