Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 24, 2019, 06:34 PM
  • 15 0778_15 0777_1242019_103753.mp4

Date
01/24/2019
W/O
0749483
Weather
Damp
Operator/Surveyor
FRANKLIN
Sewer ID
Z00593
PipeID
P12979
Time
10:34 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7903
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190118DF_ARCADIA_SIERRA_MADRE_TR_SECTS_2_5
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
15 0778
Downstream MH
15 0777
Dir. of Survey
Downstream
Length Surveyed
386.8 ft.
Total Length
386.8 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
2
O&M Quick
3122
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
14
Pipe schematic from manhole 15 0778 to 15 0777
MH: 15 0778MH: 15 0777downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 10:36 AM0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open63.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open90.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 4"100.2 ft. RTB - Roots Tap Barrell, at 02 o'clock, 10 %, within 8 inches of joint: YES100.2 ft. MGP - General Photograph - 100% ROOTS/LATERAL102 ft. MGP - General Photograph124.5 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4" - 95% ROOTS/LATERAL151.7 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open257.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open266.9 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - 75% GREASE/LATERAL303.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% GREASE/LATERAL306.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open326.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES355.8 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: YES, 4" - 35% GREASE/LATERAL383.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish383.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish386.8 ft. MGO - General Observation - Grease Throughout The Reach (5%)386.8 ft. AMH - Downstream Manhole, Survey Ends - 11:07 AM

Observation photos (8)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Tap Barrell, at 02 o'clock, 10 %, within 8 inches of joint: YES

    100.2 ft. - Roots Tap Barrell, at 02 o'clock, 10 %, within 8 inches of joint: YES

  • General Photograph - 100% ROOTS/LATERAL

    100.2 ft. - General Photograph - 100% ROOTS/LATERAL

  • General Photograph

    102 ft. - General Photograph

  • Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4" - 95% ROOTS/LATERAL

    124.5 ft. - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 4" - 95% ROOTS/LATERAL

  • Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - 75% GREASE/LATERAL

    266.9 ft. - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - 75% GREASE/LATERAL

  • Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% GREASE/LATERAL

    303.1 ft. - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4" - 100% GREASE/LATERAL

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    326.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (24)

DistanceCodeObservation
355.8TF35% GREASE/LATERAL
0MWL
151.7TFOpen
0AMH10:36 AM
0MWM
2SSS
383.1SAV
90.9TFC
0MGOConn. @ Mh, 3 O' Clock. Active
266.9TFD75% GREASE/LATERAL
102MGP
326.4CL
303.1TFD100% GREASE/LATERAL
100.2RTB
2SAV
100.2MGP100% ROOTS/LATERAL
306.2TFOpen
386.8MGOGrease Throughout The Reach (5%)
30.2TFOpen
124.5TFA95% ROOTS/LATERAL
386.8AMH11:07 AM
383.1SSS
63.8TFOpen
257.8TFOpen

Properties (3)

custom_field_two
3
customer
LACSD
datetime
2019-01-24T10:34:49-08:00