Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2019, 09:42 AM
  • Section#1_15 0851_15 0850__1112019__I0090R.mp4

Date
01/11/2019
W/O
0748669
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00594
PipeID
P12629
Time
1:42 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0090R
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Maintenance Related
Project
20190111MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_3_2A
Material
NRCP
Shape
Circular
Height
8.399999618530273 in.
Upstream MH
15 0851
Downstream MH
15 0850
Dir. of Survey
Downstream
Length Surveyed
345.8 ft.
Total Length
345.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0851 to 15 0850
MH: 15 0851MH: 15 0850downstream0 ft. MGO - General Observation - ACTIVE 3:00 MH CONN0 ft. AMH - Upstream Manhole, Survey Begins - 3:15AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - ACTIVE 9:00 MH CONN36.9 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: YES, 6" - OPEN-60% ROOTS84.6 ft. LFZ - Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER84.6 ft. LFZ - Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER84.6 ft. MGO - General Observation - TORN LINER START84.7 ft. RMB - Roots Medium Barrell, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES - ( APPOX 12" X3")TORN LINER85.7 ft. MGO - General Observation - TORN LINER FINISH108.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN133.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN183.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN190.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN237 ft. RML - Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES237 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-100% ROOTS345.3 ft. MGO - General Observation - OPEN MH CONN 3:00345.8 ft. AMH - Downstream Manhole, Survey Ends - 4:00AM

Observation photos (7)

  • Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER

    84.6 ft. - Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER

  • Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER

    84.6 ft. - Lining Failure Other, from 02 to 04 o'clock, within 8 inches of joint: YES - TORN LINER LAYER

  • General Observation - TORN LINER START

    84.6 ft. - General Observation - TORN LINER START

  • Roots Medium Barrell, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES - ( APPOX 12" X3")TORN LINER

    84.7 ft. - Roots Medium Barrell, from 02 to 04 o'clock, 10 %, within 8 inches of joint: YES - ( APPOX 12" X3")TORN LINER

  • General Observation - TORN LINER FINISH

    85.7 ft. - General Observation - TORN LINER FINISH

  • Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

    237 ft. - Roots Medium Lateral, from 08 to 11 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-100% ROOTS

    237 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 6" - OPEN-100% ROOTS

Observations (19)

DistanceCodeObservation
237RML
36.9TBDOPEN-60% ROOTS
237TBOPEN-100% ROOTS
0MGOACTIVE 3:00 MH CONN
183.4TBOPEN
0AMH3:15AM
0MWM
345.8AMH4:00AM
84.6LFZTORN LINER LAYER
85.7MGOTORN LINER FINISH
190.3TBOPEN
84.7RMB( APPOX 12" X3")TORN LINER
133.2TBOPEN
108.9TBOPEN
84.6LFZTORN LINER LAYER
0MWL
345.3MGOOPEN MH CONN 3:00
84.6MGOTORN LINER START
0MGOACTIVE 9:00 MH CONN

Properties (6)

additional_info
POST ROOT CCTV
customer
LACSD
datetime
2019-01-11T01:42:48-08:00
documentation
MARTIN,REVELES,BRAR
is_lateral_inspection
false
lining
PVCP-Folded/Reformed