Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 17, 2019, 12:40 PM
  • Section#26_15 0791_15 0700__1172019__I0095.mp4

Date
01/17/2019
W/O
0749482
Weather
Heavy Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P12992
Time
4:40 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0095
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
11.100000381469727 in.
Upstream MH
15 0791
Downstream MH
15 0700
Dir. of Survey
Downstream
Length Surveyed
276.8 ft.
Total Length
276.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
3400
O&M Rating
12
Overall Index
3
Overall Quick
Overall Rating
12
Pipe schematic from manhole 15 0791 to 15 0700
MH: 15 0791MH: 15 0700downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:45AM68.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 6" - OPEN141 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN-70% ROOTS141 ft. RML - Roots Medium Lateral, from 02 to 04 o'clock, 5 %, within 8 inches of joint: NO198.3 ft. RML - Roots Medium Lateral, from 02 to 04 o'clock, 5 %, within 8 inches of joint: NO198.3 ft. TBD - Tap Break-In Defective, at 02 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN 99% ROOTS200.3 ft. MGO - General Observation - 11.1" NRCP- CIPP LINER225.5 ft. MGO - General Observation - POSSIBLE OLD COATING SPORATIC ON PIPE264.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN276.4 ft. MGO - General Observation - ACTIVE MH CONN 3:00276.8 ft. AMH - Downstream Manhole, Survey Ends - 5:10AM

Observation photos (2)

  • General Observation - 11.1" NRCP- CIPP LINER

    200.3 ft. - General Observation - 11.1" NRCP- CIPP LINER

  • General Observation - POSSIBLE OLD COATING SPORATIC ON PIPE

    225.5 ft. - General Observation - POSSIBLE OLD COATING SPORATIC ON PIPE

Observations (13)

DistanceCodeObservation
141TBDOPEN-70% ROOTS
141RML
276.4MGOACTIVE MH CONN 3:00
0MWM
200.3MGO11.1" NRCP- CIPP LINER
0MWL
198.3RML
198.3TBDOPEN 99% ROOTS
68.6TBOPEN
276.8AMH5:10AM
225.5MGOPOSSIBLE OLD COATING SPORATIC ON PIPE
264.7TBOPEN
0AMH4:45AM

Properties (7)

custom_field_three
CIPP LINING GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-17T04:40:09-08:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false
lining
CIPP