Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 15, 2019, 08:39 AM
  • Section#8_15 1148_15 0801__1152019__I0093.mp4

Date
01/15/2019
W/O
0749482
Weather
Light Rain
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P13003
Time
12:39 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0093
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
14.199999809265137 in.
Upstream MH
15 0801
Downstream MH
15 1148
Dir. of Survey
Upstream
Length Surveyed
185.9 ft.
Total Length
185.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
4
O&M Quick
4131
O&M Rating
7
Overall Index
4
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0801 to 15 1148
MH: 15 0801MH: 15 1148upstream0 ft. AMH - Upstream Manhole, Survey Ends - 12:50AM STOPLOG IN PLACE119.1 ft. TBD - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN-99% ROOTS119.1 ft. RBL - Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO177.8 ft. MGO - General Observation - 14.2" NRCP-CIPP LINER185.9 ft. MWL - Water Level, 0 %of cross sectional area - NO FLOW STOPLOG UPSTREAM185.9 ft. MWM - Water Mark, 20 %of cross sectional area185.9 ft. AMH - Downstream Manhole, Survey Begins - 12:35AM

Observation photos (4)

  • General Observation - 14.2" NRCP-CIPP LINER

    8.1 ft. - General Observation - 14.2" NRCP-CIPP LINER

  • Tap Break-In Defective, at 11 o'clock, -,  , within 8 inches of joint: NO, 6" - OPEN-99% ROOTS

    66.8 ft. - Tap Break-In Defective, at 11 o'clock, -, , within 8 inches of joint: NO, 6" - OPEN-99% ROOTS

  • Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO

    66.8 ft. - Roots Ball Lateral, from 06 to 12 o'clock, 55 %, within 8 inches of joint: NO

  • Upstream Manhole, Survey Ends - 12:50AM STOPLOG IN PLACE

    185.9 ft. - Upstream Manhole, Survey Ends - 12:50AM STOPLOG IN PLACE

Observations (7)

DistanceCodeObservation
0MWLNO FLOW STOPLOG UPSTREAM
66.8TBDOPEN-99% ROOTS
0MWM
66.8RBL
185.9AMH12:50AM STOPLOG IN PLACE
8.1MGO14.2" NRCP-CIPP LINER
0AMH12:35AM

Properties (8)

additional_info
REVERSE INSPECTION
custom_field_three
LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-15T00:39:00-08:00
documentation
MARTIN,REVELES,OLIVER 111,BRAR
is_lateral_inspection
false
lining
CIPP