Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 14, 2019, 08:48 AM
  • Section#2_15 0811_15 0810__1142019__I0091.mp4

Date
01/14/2019
W/O
0749482
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P13012
Time
12:48 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0091
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
11.460000038146973 in.
Upstream MH
15 0811
Downstream MH
15 0810
Dir. of Survey
Downstream
Length Surveyed
265.7 ft.
Total Length
265.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
3
O&M Quick
4132
O&M Rating
10
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 15 0811 to 15 0810
MH: 15 0811MH: 15 0810downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM8.8 ft. RML - Roots Medium Lateral, from 12 to 04 o'clock, 15 %, within 8 inches of joint: NO8.8 ft. TBD - Tap Break-In Defective, at 01 o'clock, -, , within 8 inches of joint: NO, 6" - OPEM-95% ROOTS12.9 ft. MGO - General Observation - 12" NRCP +CIPP LINER52.1 ft. RMB - Roots Medium Barrell, at 11 o'clock, 5 %, within 8 inches of joint: NO52.1 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - ACTIVE97 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 6" - OPEN211.9 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 6" - OPEN222 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 6" - OPEN265.2 ft. MGO - General Observation - MH CONN 9:00 ACTIVE265.7 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observation photos (1)

  • General Observation - 12" NRCP +CIPP LINER

    12.9 ft. - General Observation - 12" NRCP +CIPP LINER

Observations (13)

DistanceCodeObservation
97TBOPEN
52.1RMB
8.8RML
0MWM
52.1TBACTIVE
0MWL
8.8TBDOPEM-95% ROOTS
0AMH12:50AM
211.9TBOPEN
12.9MGO12" NRCP +CIPP LINER
265.7AMH1:15AM
222TBOPEN
265.2MGOMH CONN 9:00 ACTIVE

Properties (7)

custom_field_three
LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-14T00:48:54-08:00
documentation
MARTIN,REVELES,BRAR
is_lateral_inspection
false
lining
CIPP