Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 11, 2019, 12:58 PM
  • Section#1_15 0812_15 0811__1112019__I0091.mp4

Date
01/11/2019
W/O
0749482
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00593
PipeID
P13013
Time
4:58 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
I0091
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111MDM_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_2_5
Material
NRCP
Shape
Circular
Height
11.460000038146973 in.
Upstream MH
15 0812
Downstream MH
15 0811
Dir. of Survey
Downstream
Length Surveyed
268.2 ft.
Total Length
268.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3211
O&M Rating
7
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0812 to 15 0811
MH: 15 0812MH: 15 0811downstream0 ft. AMH - Upstream Manhole, Survey Begins - 5:15AM0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area2.4 ft. MGO - General Observation - ACTIVE MH CONN 9:0085.8 ft. MGO - General Observation - 11.45" NRCP +CIPP98.1 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - OPEN-25% ROOTS232.5 ft. TBD - Tap Break-In Defective, at 10 o'clock, -, , within 8 inches of joint: YES, 6" - OPEN-90% ROOTS232.5 ft. RFL - Roots Fine Lateral, at 10 o'clock - 3%268.2 ft. AMH - Downstream Manhole, Survey Ends - 5:35AM

Observation photos (1)

  • General Observation - 11.45" NRCP +CIPP

    85.8 ft. - General Observation - 11.45" NRCP +CIPP

Observations (9)

DistanceCodeObservation
85.8MGO11.45" NRCP +CIPP
0AMH5:15AM
268.2AMH5:35AM
0MWL
232.5TBDOPEN-90% ROOTS
2.4MGOACTIVE MH CONN 9:00
232.5RFL3%
0MWM
98.1TBDOPEN-25% ROOTS

Properties (8)

custom_field_three
LINER GOOD COND
custom_field_two
4
customer
LACSD
datetime
2019-01-11T04:58:45-08:00
documentation
MARTIN,REVELES,BRAR
is_lateral_inspection
false
lining
CIPP
year_laid
20020918