Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2019, 07:25 PM
  • 15 0858_15 0857_1162019_112725.mp4

Date
01/16/2019
W/O
0749485
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P12636
Time
11:25 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7898
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111DF_ARCADIA_SIERRA_MADRE_TR_SECTS_3_2A
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0858
Downstream MH
15 0857
Dir. of Survey
Downstream
Length Surveyed
334.5 ft.
Total Length
334.5 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
5
Pipe schematic from manhole 15 0858 to 15 0857
MH: 15 0858MH: 15 0857downstream0 ft. AMH - Upstream Manhole, Survey Begins - 11:26 AM0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.6 ft. LFW - Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Start46.4 ft. RFJ - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR - 45% ROOTS LATERAL49.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open79.5 ft. TBA - Tap Break-In Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"123.7 ft. MGP - General Photograph134 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open162.4 ft. RFJ - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR - 10% ROOTS197.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open203.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 4" - Open230.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open233.4 ft. TFA - Tap Factory Made Active, at 09 o'clock, -, within 8 inches of joint: YES, 4"282.4 ft. MGP - General Photograph303.2 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4"331.4 ft. LFW - Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish333 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active334.5 ft. AMH - Downstream Manhole, Survey Ends - 11:54 AM334.5 ft. MGO - General Observation - Grease Throughout The Reach (5%)

Observation photos (5)

  • Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR - 45% ROOTS LATERAL

    46.4 ft. - Roots Fine Joint, at 10 o'clock, within 8 inches of joint: YESR - 45% ROOTS LATERAL

  • General Photograph

    123.7 ft. - General Photograph

  • Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR - 10% ROOTS

    162.4 ft. - Roots Fine Joint, at 12 o'clock, within 8 inches of joint: YESR - 10% ROOTS

  • General Photograph

    282.4 ft. - General Photograph

Observations (20)

DistanceCodeObservation
331.4LFW
134TFOpen
303.2TFA
162.4RFJ10% ROOTS
197.2TFOpen
0AMH11:26 AM
334.5AMH11:54 AM
230.8TFOpen
0MWM
79.5TBA
0MWL
49.3TFOpen
333MGOConn. @ Mh, 9 O' Clock. Active
282.4MGP
203.3TFOpen
46.4RFJ45% ROOTS LATERAL
2.6LFW
123.7MGP
334.5MGOGrease Throughout The Reach (5%)
233.4TFA

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-01-16T11:25:44-08:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false