Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 16, 2019, 05:33 PM
  • 15 0859_15 0858_1162019_110349.mp4

Date
01/16/2019
W/O
0749485
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00594
PipeID
P12637
Time
9:33 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7898
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 3&2A
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
20190111DF_ARCADIA_SIERRA_MADRE_TR_SECTS_3_2A
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Upstream MH
15 0859
Downstream MH
15 0858
Dir. of Survey
Downstream
Length Surveyed
335.8 ft.
Total Length
335.8 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 15 0859 to 15 0858
MH: 15 0859MH: 15 0858downstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 11:00 AM0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. LFW - Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Start59.9 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - Open108.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open171.3 ft. MGP - General Photograph205.4 ft. MGP - General Photograph223.4 ft. TFD - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open302 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 4"304.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4" - Open333.5 ft. LFW - Lining Failure Wrinkled, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish334 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)335.8 ft. AMH - Downstream Manhole, Survey Ends - 11:24 AM

Observation photos (5)

  • Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - Open

    59.9 ft. - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 4" - Open

  • Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open

    108.9 ft. - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4" - Open

  • General Photograph

    171.3 ft. - General Photograph

  • General Photograph

    205.4 ft. - General Photograph

  • Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open

    223.4 ft. - Tap Factory Made Defective, at 09 o'clock, -, within 8 inches of joint: YES, 4" - Open

Observations (15)

DistanceCodeObservation
205.4MGP
335.8AMH11:24 AM
0MWM
334MGOGREASE THROUGHOUT THE REACH (5%)
171.3MGP
0MGOConn. @ Mh, 3 O' Clock. Active
108.9TFOpen
302TFA
0AMH11:00 AM
223.4TFDOpen
59.9TFDOpen
2LFW
0MWL
304.7TFOpen
333.5LFW

Properties (5)

custom_field_two
4
customer
LACSD
datetime
2019-01-16T09:33:14-08:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false