Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2019, 05:10 PM
  • F 0077_F 0076_1102019_093921.mp4

Date
01/10/2019
W/O
0729728
Weather
Dry
Operator/Surveyor
FRANKLIN
Sewer ID
Z00035
PipeID
P10173
Time
9:10 AM
Certificate
U-415-06024039
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
G7891
Sewer Name
F JOINT OUTFALL F - UNIT 3A
City
CERRITOS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
39
Purpose
Capital Improvement Program Assesment
Project
20190110DF_JOINT_OUTFALL_F_UNIT_3A
Material
Reinforced Concrete Pipe
Shape
Circular
Height
60 in.
Upstream MH
F 0077
Downstream MH
F 0076
Dir. of Survey
Downstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
5
Pipe schematic from manhole F 0077 to F 0076
MH: F 0077MH: F 0076downstream0 ft. AMH - Upstream Manhole, Survey Begins - 9:26 AM0.1 ft. MWL - Water Level, 20 %of cross sectional area0.1 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. MGO - General Observation - Peeling & Flaking Throughout The Reach2 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES2 ft. MGO - General Observation - GREASE THROUGHOUT THE REACH (5%)2 ft. MGP - General Photograph - ZOOMED2 ft. MGP - General Photograph2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. AMH - Downstream Manhole, Survey Ends - 9:55 AM

Observation photos (5)

  • Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG

    2 ft. - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: YES - 25% MAG

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

  • General Photograph - ZOOMED

    2 ft. - General Photograph - ZOOMED

  • General Photograph

    2 ft. - General Photograph

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

    2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
0AMH9:26 AM
2MGOPeeling & Flaking Throughout The Reach
2SZ25% MAG
2SAV
0.1MWL
2MGOGREASE THROUGHOUT THE REACH (5%)
0.1MWM
2.1AMH9:55 AM
2MGPZOOMED
2MGP
2SSS

Properties (5)

custom_field_two
5
customer
LACSD
datetime
2019-01-10T09:10:53-08:00
documentation
FRANKLIN, IGNACIO, CASTILLO, RUVALCABA
is_lateral_inspection
false