Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2018, 10:10 AM
  • B 0714_B 0713 _14092018_031019.mp4

Date
09/14/2018
W/O
724243
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09387
Time
3:10 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6106
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_724243_TV15057_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0713
Downstream MH
B 0714
Dir. of Survey
Upstream
Length Surveyed
327.1 ft.
Total Length
327.1 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
195
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
195
Pipe schematic from manhole B 0713 to B 0714
MH: B 0713MH: B 0714upstream0 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish0 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - B 07140 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK97.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"100.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"148 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"151.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"199.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"203 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"248.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"251.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"299.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"302.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"324.7 ft. MGO - General Observation - MAG COAT324.7 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start327.1 ft. MWM - Water Mark, 20 %of cross sectional area327.1 ft. AMH - Downstream Manhole, Survey Begins - B 0713327.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
327.1SAV
327.1MGOCONNECTION AT MH 12 O'CLOCK
127.4TFC
25TF
27.2TFC
327.1AMHB 0714
124.1TF
2.4MGOMAG COAT
0MWM
230TFC
0AMHB 0713
0MWL
179.1TFC
2.4SAV
175.5TF
79TF
226.3TFC
75.6TF
327.1MGOCONNECTION AT MH 3 O'CLOCK

Properties (4)

additional_info
SC364822
custom_field_two
4
customer
LACSD
datetime
2018-09-14T03:10:01-07:00