Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 14, 2018, 08:13 AM
  • B 0718A_B 0718 _14092018_011458.mp4

Date
09/14/2018
W/O
724243
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09393
Time
1:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6106
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
08
Purpose
Routine Assessment
Project
WO_724243_TV15057_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0718A
Downstream MH
B 0718
Dir. of Survey
Downstream
Length Surveyed
259.9 ft.
Total Length
259.9 ft.
Structural Index
3
Structural Quick
3I00
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole B 0718A to B 0718
MH: B 0718AMH: B 0718downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - B 0718A0 ft. MWL - Water Level, 5 %of cross sectional area2.1 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.3 ft. MGO - General Observation - MAG COAT4.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"8.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"57.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"99.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"102.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"159.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"209.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.9 ft. AMH - Downstream Manhole, Survey Ends - B 0718259.9 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
205.6TFC
259.9AMHB 0718
54.5TFC
99.3TFC
259.9SAV
0MWM
2.1SAV
0MGOCONNECTION AT MH 3 O'CLOCK
8.4TFC
209.1TF
102.7TFC
0AMHB 0718A
2.3MGOMAG COAT
4.9TFC
247.5TF
159.9TFC
250.9TFC
11.5TF
153.9TFA
57.7TF
0MWL

Properties (4)

additional_info
SC364822
custom_field_two
3
customer
LACSD
datetime
2018-09-14T01:13:29-07:00