Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 18, 2018, 10:29 AM
  • B 0684_B 0683 _18092018_032957.mp4

Date
09/18/2018
W/O
724243
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00110
PipeID
P09354
Time
3:29 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6107
Sewer Name
B JOINT OUTFALL B - UNIT 8G
City
DUARTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
09
Purpose
Routine Assessment
Project
WO_724243_TV15057_SEP2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
B 0684
Downstream MH
B 0683
Dir. of Survey
Downstream
Length Surveyed
276.8 ft.
Total Length
276.8 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole B 0684 to B 0683
MH: B 0684MH: B 0683downstream0 ft. AMH - Upstream Manhole, Survey Begins - B 06840 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2.2 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start2.2 ft. MGO - General Observation - MAG COAT276.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK276.8 ft. AMH - Downstream Manhole, Survey Ends - B 0683276.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
0AMHB 0684
276.8MGOCONNECTION AT MH 3 O'CLOCK
276.8AMHB 0683
0MWM
0MWL
2.2SAV
2.2MGOMAG COAT
276.8SAV

Properties (4)

additional_info
SC364823
custom_field_two
4
customer
LACSD
datetime
2018-09-18T03:29:34-07:00