Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.00218-10-24 07:27:58 (?)
  • H 0937H 0936 District 21_112118091848.mpg

Date
10/23/0218
W/O
708172
Weather
Dry
Operator/Surveyor
B. FUGATE
Sewer ID
Z01005
PipeID
P15350
Time
11:35 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6185
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
CITY OF INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
33
Purpose
Routine Assessment
Project
WO_718172_TV21087_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
H 0937
Downstream MH
H 0936
Dir. of Survey
Downstream
Length Surveyed
464.3 ft.
Total Length
464.3 ft.
Structural Index
3
Structural Quick
3Q00
Structural Rating
267
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole H 0937 to H 0936
MH: H 0937MH: H 0936downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 09370 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area6.9 ft. MGO - General Observation - MAG COATING20.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start464.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish464.3 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK464.3 ft. AMH - Downstream Manhole, Survey Ends - H 0936

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
6.9MGOMAG COATING
20.6SAV
0AMHH 0937
464.3SAV
464.3MGOCONNECTION AT MH 3 O'CLOCK
0MWL
464.3AMHH 0936
0MWM

Properties (5)

additional_info
SC365228
customer
LACSD
datetime
0218-10-23T23:35:00-07:52
documentation
PROPIPE
is_lateral_inspection