Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jul 31, 2018, 07:03 AM
  • H 0991_H 0990 _07312018_000322.mp4

Date
07/31/2018
W/O
718172
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01005
PipeID
P15405
Time
12:03 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5884
Sewer Name
H JOINT OUTFALL H - UNIT 7C
City
INDUSTRY
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 21
Page No.
35
Purpose
Routine Assessment
Project
WO_718172_TV21087_AUG2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
H 0991
Downstream MH
H 0990
Dir. of Survey
Downstream
Length Surveyed
455.4 ft.
Total Length
455.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2Q00
O&M Rating
180
Overall Index
2
Overall Quick
Overall Rating
180
Pipe schematic from manhole H 0991 to H 0990
MH: H 0991MH: H 0990downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - MAG COATING THROUGHOUT 85%0 ft. AMH - Upstream Manhole, Survey Begins - H 09910 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start52.5 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"157.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"454.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish454.3 ft. MGO - General Observation - COCKROACHES IN MANHOLE455.4 ft. AMH - Downstream Manhole, Survey Ends - H 0990455.4 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    454.3 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
2DAGS
52.5TBA
454.3DAGS
455.4AMHH 0990
454.3MGOCOCKROACHES IN MANHOLE
0MWM
0MGOCOCKROACHES IN MANHOLE
455.4MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0MGOMAG COATING THROUGHOUT 85%
0AMHH 0991
0MWL
157.3TFC

Properties (5)

additional_info
SC364752
customer
LACSD
datetime
2018-07-31T00:03:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false