Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 3, 2019, 01:06 PM
  • 15 0830_15 0829_132019_050916.mp4

Date
01/03/2019
W/O
PENDING
Weather
Dry
Operator/Surveyor
REVELES
Sewer ID
Z00593
PipeID
P13031
Time
5:06 AM
Certificate
U-115-06022630
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1094
Sewer Name
15 ARCADIA-SIERRA MADRE TRUNK, SECTS 2&5
City
SIERRA MADRE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
01
Purpose
Routine Assessment
Project
01032019VMR_ARCADIA_SIERRA_MADRE_TRUNK_SECTS_1_AND_2
Material
NRCP
Shape
Circular
Height
9.289999961853027 in.
Upstream MH
15 0830
Downstream MH
15 0829
Dir. of Survey
Downstream
Length Surveyed
229.9 ft.
Total Length
229.9 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 15 0830 to 15 0829
MH: 15 0830MH: 15 0829downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05:15 AM1.7 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Start - COATING1.7 ft. LFB - Lining Failure Blistered, at 12 o'clock, within 8 inches of joint: NO151.2 ft. LFW - Lining Failure Wrinkled, at 02 o'clock, within 8 inches of joint: NO227.8 ft. SZ - Surface Other, from 08 to 04 o'clock, within 8 inches of joint: NO, Finish - COAT229.9 ft. AMH - Downstream Manhole, Survey Ends - 05:32 AM

Observation photos (1)

  • Lining Failure Blistered, at 12 o'clock, within 8 inches of joint: NO

    1.7 ft. - Lining Failure Blistered, at 12 o'clock, within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
1.7SZCOATING
1.7LFB
0MWM
0MWL
229.9AMH05:32 AM
227.8SZCOAT
0AMH05:15 AM
151.2LFW

Properties (4)

custom_field_two
3
customer
LACSD
datetime
2019-01-03T05:06:34-08:00
lining
CIPP