Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 4, 2018, 11:19 AM
  • 01 0664_01 0663_20180904_044431.mp4

Date
09/04/2018
W/O
723858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01372
Time
4:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5993
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
LYNWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_723858_TV01117_SEP2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
48 in.
Width
48 in.
Upstream MH
01 0664
Downstream MH
01 0663
Dir. of Survey
Downstream
Length Surveyed
405.5 ft.
Total Length
405.5 ft.
Structural Index
4
Structural Quick
5O3O
Structural Rating
643
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
643
Pipe schematic from manhole 01 0664 to 01 0663
MH: 01 0664MH: 01 0663downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 06640 ft. MGO - General Observation - CONNECTION AT MH 2 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start404.5 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish405.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0663

Observation photos (2)

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
405.4SAP
2.1SRV
0AMH01 0664
0MGOCONNECTION AT MH 2 O'CLOCK
0MWL
405.5AMH01 0663
404.5SRV
2.1SAP
0MWM

Properties (6)

additional_info
SC364807
custom_field_two
2
customer
LACSD
datetime
2018-09-04T04:19:17-07:00
documentation
PRO PIPE
is_lateral_inspection
false