Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2018, 08:18 AM
  • 01 0676_01 0675_20180830_013134.mp4

Date
08/30/2018
W/O
723858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01385
Time
1:18 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5991
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
South Gate
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_723858_TV01117_SEP2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0676
Downstream MH
01 0675
Dir. of Survey
Downstream
Length Surveyed
402.9 ft.
Total Length
402.9 ft.
Structural Index
4
Structural Quick
5O3O
Structural Rating
640
O&M Index
2
O&M Quick
2600
O&M Rating
12
Overall Index
4
Overall Quick
Overall Rating
652
Pipe schematic from manhole 01 0676 to 01 0675
MH: 01 0676MH: 01 0675downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06762.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start372.7 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Start402.9 ft. SRV - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.9 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO, Finish402.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK402.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0675402.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish402.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
402.9SRV
0MWL
0MWM
402.9DSZ
0AMH01 0676
2.6SAP
402.9MGOCONNECTION AT MH 9 O'CLOCK
402.9AMH01 0675
402.9SAP
402.9MGOCONNECTION AT MH 3 O'CLOCK
372.7DSZ
2.6SRV

Properties (6)

additional_info
SC364805
custom_field_two
2
customer
LACSD
datetime
2018-08-30T01:18:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false