Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 30, 2018, 06:37 AM
  • 01 0680_01 0679_20180829_235253.mp4

Date
08/29/2018
W/O
723858
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00199
PipeID
P01389
Time
11:37 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K5991
Sewer Name
01 CALIFORNIA AVENUE EXTENSION TRUNK
City
South Gate
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
14
Purpose
Routine Assessment
Project
WO_723858_TV01117_SEP2018
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
33 in.
Upstream MH
01 0680
Downstream MH
01 0679
Dir. of Survey
Downstream
Length Surveyed
473.5 ft.
Total Length
473.5 ft.
Structural Index
3
Structural Quick
513R
Structural Rating
289
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
289
Pipe schematic from manhole 01 0680 to 01 0679
MH: 01 0680MH: 01 0679downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 06800 ft. MWM - Water Mark, 35 %of cross sectional area3.5 ft. MGO - General Observation - MAG COAT3.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38.4 ft. SSS - Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO90.3 ft. SRV - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO473.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK473.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish473.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0679

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO

    38.4 ft. - Surface Spalling, from 02 to 03 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

    90.3 ft. - Surface Reinforcement Visible, from 02 to 04 o'clock, within 8 inches of joint: NO

Observations (10)

DistanceCodeObservation
3.5MGOMAG COAT
38.4SSS
0MWL
473.5MGOCONNECTION AT MH 9 O'CLOCK
473.5SAP
90.3SRV
473.5AMH01 0679
0AMH01 0680
0MWM
3.5SAP

Properties (6)

additional_info
SC364805
custom_field_two
2
customer
LACSD
datetime
2018-08-29T23:37:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false