Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2018, 10:19 AM
  • 02 1440_02 1439_14112018_022055.mp4

Date
11/14/2018
W/O
734965
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00307
PipeID
P04679
Time
2:19 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6221
Sewer Name
02 TRACT #5445 TRUNK
City
COMMERCE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_734965_TV02302_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1440
Downstream MH
02 1439
Dir. of Survey
Downstream
Length Surveyed
359.6 ft.
Total Length
359.6 ft.
Structural Index
3
Structural Quick
453M
Structural Rating
235
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
235
Pipe schematic from manhole 02 1440 to 02 1439
MH: 02 1440MH: 02 1439downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 14404.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES9.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.8 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES125 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES, Start139.9 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"142.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"148.3 ft. FM - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES, Finish213.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"252.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 3"265.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"359.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish359.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1439

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    4.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    33.8 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES, Start

    125 ft. - Fracture Multiple, from 09 to 01 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"

    139.9 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    265.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

Observations (15)

DistanceCodeObservation
265.5TB
125FM
9.3CM
252.9TFC
0MWL
359.5CM
0MWM
148.3FM
33.8FC
359.6AMH02 1439
0AMH02 1440
213.4TF
142.2TFC
139.9TB
4.1CM

Properties (4)

additional_info
SC365249
custom_field_two
3
customer
LACSD
datetime
2018-11-14T02:19:20-08:00