Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2018, 05:42 AM
  • 30 0155_30 0154 _19112018_214223.mp4

Date
11/19/2018
W/O
735497
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17860
Time
9:42 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6225
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_735497_TV30073_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0155
Downstream MH
30 0154
Dir. of Survey
Downstream
Length Surveyed
290.9 ft.
Total Length
290.9 ft.
Structural Index
3
Structural Quick
3I21
Structural Rating
148
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
148
Pipe schematic from manhole 30 0155 to 30 0154
MH: 30 0155MH: 30 0154downstream0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 30 015514.3 ft. CC - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES19 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES27.1 ft. CC - Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES50.8 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES55.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start77.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"290.9 ft. AMH - Downstream Manhole, Survey Ends - 30 0154290.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish290.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (5)

  • Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    14.3 ft. - Crack Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    19 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

    27.1 ft. - Crack Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    50.8 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    55.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
14.3CC
203.6TF
290.9AMH30 0154
0MGOCONNECTION AT MH 3 O'CLOCK
55.7CM
290.9CM
267.1TF
0MWL
19CL
290.9MGOCONNECTION AT MH 9 O'CLOCK
50.8CM
0MWM
0AMH30 0155
142.1TF
27.1CC
77.2TF

Properties (4)

additional_info
SC365453
custom_field_two
3
customer
LACSD
datetime
2018-11-19T21:42:18-08:00