Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 20, 2018, 06:03 AM
  • 30 0153_30 0152 _19112018_220312.mp4

Date
11/19/2018
W/O
735497
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00878
PipeID
P17858
Time
10:03 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6225
Sewer Name
30 SOUTH BAY CITIES MAIN TRUNK
City
REDONDO BEACH
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 30
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_735497_TV30073_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
30 0153
Downstream MH
30 0152
Dir. of Survey
Downstream
Length Surveyed
289.5 ft.
Total Length
289.5 ft.
Structural Index
3
Structural Quick
423I
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole 30 0153 to 30 0152
MH: 30 0153MH: 30 0152downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 30 01535.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES6.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"20 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES36.7 ft. CC - Crack Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES48.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"113.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"160.5 ft. FM - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES181.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK289.5 ft. AMH - Downstream Manhole, Survey Ends - 30 0152289.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    5.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    20 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

    36.7 ft. - Crack Circumferential, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    48.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    113.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

    160.5 ft. - Fracture Multiple, from 11 to 03 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
48.4CM
113.5TB
0MWM
181.8TF
248.8TF
289.5MGOCONNECTION AT MH 3 O'CLOCK
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
160.5FM
6.1TF
36.7CC
49.6TF
20CM
5.3FM
289.5AMH30 0152
289.5CM
0AMH30 0153

Properties (4)

additional_info
SC365453
custom_field_two
3
customer
LACSD
datetime
2018-11-19T22:03:09-08:00