Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 21, 2018, 09:02 AM
  • 08 0071_08 0070_12212018_013342.mp4

Date
12/21/2018
W/O
O743258
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00016
PipeID
P00073
Time
1:02 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1087
Sewer Name
08 MAIN STREET TRUNK
City
COMPTON
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
02
Purpose
Capital Improvement Program Assesment
Project
20181221MDM_MAIN_STREET_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
08 0071
Downstream MH
08 0070
Dir. of Survey
Downstream
Length Surveyed
332.9 ft.
Total Length
332.9 ft.
Structural Index
2
Structural Quick
322C
Structural Rating
46
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
46
Pipe schematic from manhole 08 0071 to 08 0070
MH: 08 0071MH: 08 0070downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 1:30AM6 ft. FL - Fracture Longitudinal, at 09 o'clock, within 8 inches of joint: YES - HAIRLINE8.3 ft. MGO - General Observation - 15" VCP11.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES15.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - H17.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H19 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped20.3 ft. FL - Fracture Longitudinal, at 08 TO 4 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS20.3 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - HAIRLINE AT JOINTS26.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SLIGHT29.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL67.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Active72 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL102.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL114.7 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL118.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped126.4 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL162.8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL165.8 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL169.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped174.1 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL205 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL211.5 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL214.7 ft. FC - Fracture Circumferential, from 08 to 02 o'clock, within 8 inches of joint: YES - SL218.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open226.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL267.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped302.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL308.5 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL311.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL322.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open332.6 ft. FL - Fracture Longitudinal, at 08 o'clock, within 8 inches of joint: YES, Finish - 15% HAIRLINE AT JOINTS332.6 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish - 70% HAIRLINE AT JOINTS332.9 ft. AMH - Downstream Manhole, Survey Ends - 2:05AM

Observation photos (1)

  • General Observation - 15" VCP

    8.3 ft. - General Observation - 15" VCP

Observations (36)

DistanceCodeObservation
332.6FL15% HAIRLINE AT JOINTS
20.3FLHAIRLINE AT JOINTS
8.3MGO15" VCP
162.8FCSL
72FCSL
19TFCCapped
0MWM
17.7FCH
174.1FCSL
15.1FCH
0MWL
26.7FCSLIGHT
118.8TFCCapped
6FLHAIRLINE
29.9FCSL
311.9FCSL
114.7FCSL
205FCSL
332.9AMH2:05AM
322.1TFOpen
218.8TFOpen
267.7TFCCapped
211.5FCSL
165.8FCSL
308.5FCSL
302.4FCSL
102.6FCSL
11.4FC
67.6TFActive
214.7FCSL
126.4FCSL
0AMH1:30AM
20.3FCHAIRLINE AT JOINTS
226.1FCSL
332.6FC70% HAIRLINE AT JOINTS
169.8TFCCapped

Properties (4)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2018-12-21T01:02:12-08:00