- Date
- 12/18/2018
- W/O
- 0731413
- Weather
- Dry
- Operator/Surveyor
- SANTIAGO OBREGON
- Sewer ID
- Z00323
- PipeID
- P08135
- Time
- 8:55 AM
- Certificate
- U-1014-06022541
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- G7882
- Sewer Name
- A JOA-1A LOS COYOTES WRP INTERCEPTOR
- City
- DOWNEY
- Loc. details
- Main Highway - Suburban/Rural
- Location Code
- B
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 29
- Purpose
- Routine Assessment
- Project
- 20181218SHO_JOA1A_LOS_COYOTES_WRP_INTERCEPTOR
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 78 in.
- Upstream MH
- A 0200A
- Downstream MH
- A 0200
- Dir. of Survey
- Downstream
- Length Surveyed
- 767.8 ft.
- Total Length
- 767.8 ft.
- Structural Index
- 3
- Structural Quick
- 3121
- Structural Rating
- 5
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 5
Pipe schematic from manhole A 0200A to A 0200 Observation photos (3)

8 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES

306.6 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

402.6 ft. - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 8"