08 0467_08 0466_12192018_012617.mp4
2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG AREAS OF MISSING TILES
2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR
2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR COEEISON BEYOUND REBAR
19 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: YES - BROKEN REBAR CORRISON BEYOUND REBAR
19.3 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR
47.5 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - BROKEN REBAR
66.5 ft. - General Observation - 100% MISSING TILES START
101.2 ft. - Surface Reinforcement Corroded, from 09 to 03 o'clock, within 8 inches of joint: NO - CORRISON BEYOUND REBAR
136.6 ft. - General Observation - 50% TILES START
| Distance | Code | Observation |
|---|---|---|
| 158.1 | SRC | LONG & CIRCUM REBAR |
| 0 | AMH | 1:20AM |
| 2 | MGO | 95% MISSING TILES START 9:00 TO 3:00 |
| 19.3 | SRC | BROKEN REBAR |
| 2 | SAM | SEVERE AGG AREAS OF MISSING TILES |
| 158.1 | SRC | BROKEN MISSING REBAR CORRISON BEYOUND REBAR |
| 158.1 | MGO | 90% MAG COAT FINISH |
| 2 | MGO | MAG COAT 90% START 9:00 TO 2:00 |
| 158.9 | AMH | 1:55AMAM |
| 0 | MGO | Conn. @ Mh, 3 O' Clock. Active |
| 19 | SRC | BROKEN REBAR CORRISON BEYOUND REBAR |
| 101.2 | SRC | CORRISON BEYOUND REBAR |
| 98.3 | MGO | 1 ROW TILES |
| 47.5 | SRC | BROKEN REBAR |
| 66.5 | MGO | 100% MISSING TILES START |
| 0 | MWM | — |
| 158.1 | SAM | SEVERE AGG |
| 136.6 | MGO | 50% TILES START |
| 158.1 | MGO | 50% MISSING TILES FINISH |
| 2 | SRC | LONG & CIRCUM REBAR |
| 2 | SRC | BROKEN MISSING REBAR COEEISON BEYOUND REBAR |
| 128.9 | MGO | 5 ROWS TILES |
| 0 | MWL | — |
| 158.1 | MGO | Conn. @ Mh, 3 O' Clock. OPEN |