Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 18, 2018, 11:25 AM
  • 08 0470_08 0469_12182018_041353.mp4

Date
12/18/2018
W/O
0744161
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00026
PipeID
P00526
Time
3:25 AM
Certificate
U-10`4-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1076
Sewer Name
08 216TH STREET TRUNK
City
CARSON
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
10
Purpose
Capital Improvement Program Assesment
Project
20181218MDM_216TH_STREET_TRUNK
Material
RCP-CTL
Shape
Circular
Height
36 in.
Upstream MH
08 0470
Downstream MH
08 0469
Dir. of Survey
Downstream
Length Surveyed
432.9 ft.
Total Length
432.9 ft.
Structural Index
5
Structural Quick
5941
Structural Rating
49
O&M Index
5
O&M Quick
5100
O&M Rating
5
Overall Index
5
Overall Quick
Overall Rating
54
Pipe schematic from manhole 08 0470 to 08 0469
MH: 08 0470MH: 08 0469downstream0 ft. MWM - Water Mark, 80 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. MWL - Water Level, 50 %of cross sectional area2 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG AREAS OF MISSING REBAR2 ft. MGO - General Observation - 90% MISSING TILES START 10:00 TO 2:002 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR13.7 ft. MGO - General Observation - 25% MISSING TILES START35.1 ft. MGO - General Observation - 100% MISSING TILES50.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR55.4 ft. MGO - General Observation - 25% MISSING TILES START69.4 ft. MGO - General Observation - 100% MISSING TILES97.9 ft. MGO - General Observation - 100% MISSING TILES107.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUND REBAR118.7 ft. MGO - General Observation - 60% MISSING TILES START149.6 ft. MGO - General Observation - 60% MISSING TILES START211.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR271.5 ft. MGO - General Observation - 95% MISSING TILES START280.5 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR331.1 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR372.6 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR388 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR424.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR432.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - LONG & CIRCUM REBAR432.7 ft. MGO - General Observation - 95% MISSING TILES FINISH432.7 ft. SAM - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG432.7 ft. SRC - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Finish - BROKEN MISSING REBAR CORRISON BEYOUND REBAR432.9 ft. AMH - Downstream Manhole, Survey Ends - 4:55AM

Observation photos (16)

  • Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG AREAS OF MISSING REBAR

    2 ft. - Surface Aggregate Missing, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - SEVRE AGG AREAS OF MISSING REBAR

  • General Observation - 90% MISSING TILES START 10:00 TO 2:00

    2 ft. - General Observation - 90% MISSING TILES START 10:00 TO 2:00

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

    2 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - LONG & CIRCUM REBAR

  • General Observation - 25% MISSING TILES START

    13.7 ft. - General Observation - 25% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

    50.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - CIRCUM REBAR

  • General Observation - 100% MISSING TILES

    69.4 ft. - General Observation - 100% MISSING TILES

  • General Observation - 100% MISSING TILES

    97.9 ft. - General Observation - 100% MISSING TILES

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUND REBAR

    107.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: YES, Start - BROKEN MISSING REBAR CORRISON BEYOUND REBAR

  • General Observation - 60% MISSING TILES START

    118.7 ft. - General Observation - 60% MISSING TILES START

  • General Observation - 60% MISSING TILES START

    149.6 ft. - General Observation - 60% MISSING TILES START

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR

    211.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR CORRISON BEYOUND REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    280.5 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

    331.1 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR

    372.6 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - MISSING REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    388 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

  • Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

    424.7 ft. - Surface Reinforcement Corroded, from 10 to 02 o'clock, within 8 inches of joint: NO - BROKEN REBAR

Observations (28)

DistanceCodeObservation
432.7SRCLONG & CIRCUM REBAR
13.7MGO25% MISSING TILES START
0MWM
432.9AMH4:55AM
331.1SRCBROKEN MISSING REBAR
118.7MGO60% MISSING TILES START
432.7MGO95% MISSING TILES FINISH
271.5MGO95% MISSING TILES START
149.6MGO60% MISSING TILES START
2SAMSEVRE AGG AREAS OF MISSING REBAR
424.7SRCBROKEN REBAR
2MGO90% MISSING TILES START 10:00 TO 2:00
0AMH4:15AM
432.7SAMSEVERE AGG
2SRCLONG & CIRCUM REBAR
69.4MGO100% MISSING TILES
97.9MGO100% MISSING TILES
107.7SRCBROKEN MISSING REBAR CORRISON BEYOUND REBAR
388SRCBROKEN REBAR
372.6SRCMISSING REBAR
211.7SRCMISSING REBAR CORRISON BEYOUND REBAR
55.4MGO25% MISSING TILES START
50.5SRCCIRCUM REBAR
0MGOConn. @ Mh, 9 O' Clock. Active
432.7SRCBROKEN MISSING REBAR CORRISON BEYOUND REBAR
35.1MGO100% MISSING TILES
0MWL
280.5SRCBROKEN REBAR

Properties (4)

custom_field_three
CORRISON BEYOUND REBAR
custom_field_two
1
customer
LACSD
datetime
2018-12-18T03:25:08-08:00