Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2018, 10:05 AM
  • 05 1367_05 1366 _06112018_020618.mp4

Date
11/06/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06584
Time
2:05 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6210
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1366
Downstream MH
05 1367
Dir. of Survey
Upstream
Length Surveyed
318.8 ft.
Total Length
318.8 ft.
Structural Index
3
Structural Quick
3L00
Structural Rating
189
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
189
Pipe schematic from manhole 05 1366 to 05 1367
MH: 05 1366MH: 05 1367upstream0 ft. MGO - General Observation - CONNECTION AT MH 12 O'CLOCK0 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish0 ft. AMH - Upstream Manhole, Survey Ends - 05 136725.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"68.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"120 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"171.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"222.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"271.4 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"316.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start318.8 ft. AMH - Downstream Manhole, Survey Begins - 05 1366318.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK318.8 ft. MWL - Water Level, 15 %of cross sectional area318.8 ft. MWM - Water Mark, 30 %of cross sectional area

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
0AMH05 1366
2.5SAP
198.8TFC
318.8MGOCONNECTION AT MH 12 O'CLOCK
147.3TFC
250TFC
0MGOCONNECTION AT MH 9 O'CLOCK
0MWL
318.8SAP
318.8AMH05 1367
96.3TFC
0MWM
47.4TFC
293.4TF

Properties (4)

additional_info
SC365238
custom_field_two
2
customer
LACSD
datetime
2018-11-06T02:05:45-08:00