Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2018, 08:28 AM
  • 05 2413_05 1369 _06112018_003033.mp4

Date
11/06/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06588
Time
12:28 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6210
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 2413
Downstream MH
05 1369
Dir. of Survey
Downstream
Length Surveyed
300.5 ft.
Total Length
300.5 ft.
Structural Index
3
Structural Quick
4B3N
Structural Rating
275
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
276
Pipe schematic from manhole 05 2413 to 05 1369
MH: 05 2413MH: 05 1369downstream0 ft. MGO - General Observation - CONNECTION AT MH 11 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 24130 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area3.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES9.1 ft. FM - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES11.8 ft. MMC - Material Change, Concrete pipe (non-reinfored)11.8 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start21.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start46 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"46.1 ft. FM - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES46.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish61.8 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start98 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"112.6 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Finish147.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"201.3 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"247 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES, Start251.2 ft. RFC - Roots Fine Connection, at 12 o'clock251.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"300.3 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES, Finish300.4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish300.5 ft. AMH - Downstream Manhole, Survey Ends - 05 1369

Observation photos (8)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    3.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

    9.1 ft. - Fracture Multiple, from 10 to 05 o'clock, within 8 inches of joint: YES

  • Material Change, Concrete pipe (non-reinfored)

    11.8 ft. - Material Change, Concrete pipe (non-reinfored)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    11.8 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    21.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

    46.1 ft. - Fracture Multiple, from 11 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

    61.8 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES, Start

    247 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
3.9FM
46TFC
98TFC
0MGOCONNECTION AT MH 11 O'CLOCK
11.8MMC
61.8FL
46.1FM
201.3TFC
11.8SAV
0AMH05 2413
147.9TFA
247FM
9.1FM
300.4SAV
0MWM
251.2RFC
251.2TFA
46.1FL
0MWL
300.3FM
21.7FL
112.6FL
300.5AMH05 1369

Properties (4)

additional_info
SC365238
custom_field_two
2
customer
LACSD
datetime
2018-11-06T00:28:56-08:00