Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2018, 09:51 AM
  • 05 1355_05 1354 _07112018_015142.mp4

Date
11/07/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06571
Time
1:51 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6212
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1355
Downstream MH
05 1354
Dir. of Survey
Downstream
Length Surveyed
43.1 ft.
Total Length
43.1 ft.
Structural Index
3
Structural Quick
3800
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
24
Pipe schematic from manhole 05 1355 to 05 1354
MH: 05 1355MH: 05 1354downstream0 ft. MWM - Water Mark, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13550 ft. MWL - Water Level, 5 %of cross sectional area4 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start4 ft. MGO - General Observation - MAG COAT7.2 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"43 ft. SAV - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish43.1 ft. AMH - Downstream Manhole, Survey Ends - 05 1354

Observation photos (1)

  • Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Surface Aggregate Visible, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
7.2TFC
0MWM
0AMH05 1355
4SAV
43SAV
0MWL
43.1AMH05 1354
4MGOMAG COAT

Properties (4)

additional_info
SC365240
custom_field_two
3
customer
LACSD
datetime
2018-11-07T01:51:12-08:00