Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2018, 11:22 AM
  • 05 1360_05 1359 _06112018_032224.mp4

Date
11/06/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06577
Time
3:22 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6210
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1359
Downstream MH
05 1360
Dir. of Survey
Upstream
Length Surveyed
371.9 ft.
Total Length
371.9 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2111
O&M Rating
3
Overall Index
2
Overall Quick
Overall Rating
6
Pipe schematic from manhole 05 1359 to 05 1360
MH: 05 1359MH: 05 1360upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 13600.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish40 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YES40.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"136.8 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"186.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"186.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES235.8 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"284 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"336.3 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"369.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start369.8 ft. MGO - General Observation - MAG COAT371.8 ft. MWM - Water Mark, 30 %of cross sectional area371.9 ft. MWL - Water Level, 10 %of cross sectional area371.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK371.9 ft. AMH - Downstream Manhole, Survey Begins - 05 1359

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
2.1SAP
136.1TFC
185.8TFA
371.9AMH05 1360
331.9RFJ
87.9TF
185.8DAGS
0MWL
0MGOCONNECTION AT MH 3 O'CLOCK
283.3TFA
0.1MWM
2.1MGOMAG COAT
235.1TF
331.8TFA
35.6TF
371.8SAP
0AMH05 1359

Properties (4)

additional_info
SC365238
custom_field_two
2
customer
LACSD
datetime
2018-11-06T03:22:01-08:00