Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 6, 2018, 10:39 AM
  • 05 1365_05 1364 _06112018_024050.mp4

Date
11/06/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06582
Time
2:39 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6210
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1365
Downstream MH
05 1364
Dir. of Survey
Downstream
Length Surveyed
142.6 ft.
Total Length
142.6 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
84
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
84
Pipe schematic from manhole 05 1365 to 05 1364
MH: 05 1365MH: 05 1364downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 13650 ft. MWM - Water Mark, 30 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start47 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"99 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.6 ft. AMH - Downstream Manhole, Survey Ends - 05 1364142.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
47TF
99TFC
0MWL
142.6AMH05 1364
0AMH05 1365
142.6SAP
2.1SAP
0MWM

Properties (4)

additional_info
SC365238
custom_field_two
2
customer
LACSD
datetime
2018-11-06T02:39:53-08:00