Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 8, 2018, 10:58 AM
  • 05 1332A_05 1332_08112018_025849.mp4

Date
11/08/2018
W/O
735012
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00444
PipeID
P06549
Time
2:58 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6214
Sewer Name
05 GARDENA PUMP TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_735012_TV05295_NOV2018
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
05 1332A
Downstream MH
05 1332
Dir. of Survey
Downstream
Length Surveyed
160.3 ft.
Total Length
160.3 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
93
O&M Index
3
O&M Quick
3B00
O&M Rating
39
Overall Index
3
Overall Quick
Overall Rating
132
Pipe schematic from manhole 05 1332A to 05 1332
MH: 05 1332AMH: 05 1332downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 45 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 1332A3.4 ft. MGO - General Observation - MAG COAT3.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.4 ft. ID - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO82.1 ft. ID - Infiltration Dripper, from 02 to 03 o'clock, within 8 inches of joint: YES101.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"105.9 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start160.2 ft. ID - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish160.2 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK160.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish160.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1332160.3 ft. MGO - General Observation - CAPPED LATERAL 9 O'CLOCK @ MH

Observation photos (3)

  • Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO

    4.4 ft. - Infiltration Dripper, at 12 o'clock, within 8 inches of joint: NO

  • Infiltration Dripper, from 02 to 03 o'clock, within 8 inches of joint: YES

    82.1 ft. - Infiltration Dripper, from 02 to 03 o'clock, within 8 inches of joint: YES

  • Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    105.9 ft. - Infiltration Dripper, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
160.2ID
160.3AMH05 1332
101.1TF
160.2MGOCONNECTION AT MH 3 O'CLOCK
105.9ID
3.4MGOMAG COAT
3.5SAV
82.1ID
0MWL
160.3MGOCAPPED LATERAL 9 O'CLOCK @ MH
0MWM
0AMH05 1332A
160.2SAV
4.4ID

Properties (4)

additional_info
SC365242
custom_field_two
3
customer
LACSD
datetime
2018-11-08T02:58:45-08:00