Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 27, 2018, 05:30 AM
  • C 0567_C 0566_26112018_213524.mp4

Date
11/26/2018
W/O
735004
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00362
PipeID
P04751
Time
9:30 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6229
Sewer Name
C JOINT OUTFALL C - UNIT 4D
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_735004_TV03084_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
27 in.
Width
27 in.
Upstream MH
C 0567
Downstream MH
C 0566
Dir. of Survey
Downstream
Length Surveyed
348.8 ft.
Total Length
348.8 ft.
Structural Index
3
Structural Quick
3S00
Structural Rating
297
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
3
Overall Quick
Overall Rating
299
Pipe schematic from manhole C 0567 to C 0566
MH: C 0567MH: C 0566downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - C 05670 ft. MWM - Water Mark, 25 %of cross sectional area6.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start28.5 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES171.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish348.8 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK348.8 ft. AMH - Downstream Manhole, Survey Ends - C 0566348.8 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK348.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    14.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock,  , within 8 inches of joint: YES

    28.5 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 08 to 04 o'clock, , within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
6.4CM
171.2FL
0MWL
14.6FL
348.8MGOCONNECTION AT MH 9 O'CLOCK
348.8AMHC 0566
0AMHC 0567
28.5DAE
0MWM
348.8MGOCONNECTION AT MH 3 O'CLOCK
348.8CM

Properties (4)

additional_info
SC365457
custom_field_two
3
customer
LACSD
datetime
2018-11-26T21:30:25-08:00