Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2018, 09:10 AM
  • 02 1349_02 1348 _14112018_011015.mp4

Date
11/14/2018
W/O
735000
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00277
PipeID
P04623
Time
1:10 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6220
Sewer Name
02 JANE STREET BRANCH TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
RFIR_WO_735000_TV02342_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
02 1349
Downstream MH
02 1348
Dir. of Survey
Downstream
Length Surveyed
742.4 ft.
Total Length
742.4 ft.
Structural Index
3
Structural Quick
3N22
Structural Rating
232
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
232
Pipe schematic from manhole 02 1349 to 02 1348
MH: 02 1349MH: 02 1348downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 1349110.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES126.1 ft. CL - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES165.3 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES279.1 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES288 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"316.6 ft. CM - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES380.6 ft. CM - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES382.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start742.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1348742.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    110.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

    126.1 ft. - Crack Longitudinal, at 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    165.3 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    279.1 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

    316.6 ft. - Crack Multiple, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

    380.6 ft. - Crack Multiple, from 03 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    382.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
742.4AMH02 1348
0MWM
0MGOCONNECTION AT MH 9 O'CLOCK
382.7CM
165.3CM
110.3CM
316.6CM
380.6CM
279.1CL
742.4CM
0MWL
126.1CL
288TF
0AMH02 1349

Properties (4)

additional_info
SC365248
custom_field_two
3
customer
LACSD
datetime
2018-11-14T01:10:04-08:00