Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2018, 06:16 AM
  • 18 0657_18 0656 _27112018_221703.mp4

Date
11/27/2018
W/O
734990
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14506
Time
10:16 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6232
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734990_TV18081_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0657
Downstream MH
18 0656
Dir. of Survey
Downstream
Length Surveyed
324.9 ft.
Total Length
324.9 ft.
Structural Index
3
Structural Quick
453D
Structural Rating
118
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
118
Pipe schematic from manhole 18 0657 to 18 0656
MH: 18 0657MH: 18 0656downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06570 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area8.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"13.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"20 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start42.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish106.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"109.3 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start111.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"174.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish174.6 ft. CM - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES189.8 ft. CM - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES206.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"207.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start207.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"212.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"318 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish318 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES324.9 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK324.9 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK324.9 ft. AMH - Downstream Manhole, Survey Ends - 18 0656

Observation photos (7)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    20 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    109.3 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

    174.6 ft. - Crack Multiple, from 02 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    189.8 ft. - Crack Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    206.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    207.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    318 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (22)

DistanceCodeObservation
0AMH18 0657
174.6CL
0MWM
106.4TFC
324.9MGOCONNECTION AT MH 9 O'CLOCK
318CM
20FM
324.9MGOCONNECTION AT MH 3 O'CLOCK
318FM
324.9AMH18 0656
13.9TF
109.3CL
111.5TFC
174.6CM
207.4CM
42.3FM
212.2TFC
207.4TFC
0MWL
8.7TF
206.7TB
189.8CM

Properties (4)

additional_info
SC365460
custom_field_two
2
customer
LACSD
datetime