Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2018, 07:03 AM
  • 18 0667_18 0666 _27112018_230326.mp4

Date
11/27/2018
W/O
734990
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14516
Time
11:03 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6232
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734990_TV18081_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0667
Downstream MH
18 0666
Dir. of Survey
Downstream
Length Surveyed
338 ft.
Total Length
338 ft.
Structural Index
4
Structural Quick
4H31
Structural Rating
195
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
195
Pipe schematic from manhole 18 0667 to 18 0666
MH: 18 0667MH: 18 0666downstream0 ft. MGO - General Observation - HEAVY STEAM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06670 ft. MWM - Water Mark, 20 %of cross sectional area15.4 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES46.4 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start73.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"76.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish97.1 ft. SSS - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES107.7 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start111.3 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES111.3 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Finish121.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start121.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"338 ft. AMH - Downstream Manhole, Survey Ends - 18 0666338 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    15.4 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    46.4 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

    97.1 ft. - Surface Spalling, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

    107.7 ft. - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    111.3 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    121.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
73.8TFC
180.2TF
46.4CL
0MGOHEAVY STEAM
338AMH18 0666
121.1FM
0MWL
107.7FL
97.1SSS
111.3FM
338FM
15.4CL
0AMH18 0667
121.1TF
76.9CL
111.3FL
0MWM
276.7TFC

Properties (4)

additional_info
SC365460
custom_field_two
2
customer
LACSD
datetime
2018-11-27T23:03:19-08:00