Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 28, 2018, 05:41 AM
  • 18 0660_18 0659 _27112018_214533.mp4

Date
11/27/2018
W/O
734990
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14509
Time
9:41 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6232
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734990_TV18081_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
18 0660
Downstream MH
18 0659
Dir. of Survey
Downstream
Length Surveyed
336.6 ft.
Total Length
336.6 ft.
Structural Index
3
Structural Quick
4D3C
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
156
Pipe schematic from manhole 18 0660 to 18 0659
MH: 18 0660MH: 18 0659downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 06600 ft. MGO - General Observation - heavy steam0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 20 %of cross sectional area12.6 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES23.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start42.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish42.7 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start49.2 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES49.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start49.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish61.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"97.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish134.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start161.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"166.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"214.8 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start214.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish261.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"266.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish303.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES336.6 ft. AMH - Downstream Manhole, Survey Ends - 18 0659

Observation photos (8)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    12.6 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

    23.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    42.7 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    49.2 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    49.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    134.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    214.8 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    303.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
214.8FM
49.5FM
97.7FM
0AMH18 0660
0MGOheavy steam
0MWL
61.5TFC
65.8TFC
161.2TFC
42.7CL
303.7CM
273.3FM
0MGOCONNECTION AT MH 3 O'CLOCK
42.7FL
0MWM
134.1CM
49.5FL
49.2FM
12.6CL
266.9TFC
261.7TF
214.8CM
166.4TFC
336.6AMH18 0659
23.5CL

Properties (4)

additional_info
SC365460
custom_field_two
2
customer
LACSD
datetime
2018-11-27T21:41:21-08:00