Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2018, 06:34 AM
  • 18 0670_18 0669 _14112018_223409.mp4

Date
11/14/2018
W/O
734990
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14519
Time
10:34 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6224
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734990_TV18081_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0670
Downstream MH
18 0669
Dir. of Survey
Downstream
Length Surveyed
342.8 ft.
Total Length
342.8 ft.
Structural Index
3
Structural Quick
4C3F
Structural Rating
185
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
185
Pipe schematic from manhole 18 0670 to 18 0669
MH: 18 0670MH: 18 0669downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 18 06700 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - HEAVY STEAM FROM MH0 ft. MWL - Water Level, 10 %of cross sectional area28.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start49.9 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish49.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start118.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"123.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"155.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish177.6 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start220.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"225.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"248.3 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish248.4 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES, Start316.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"322.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.9 ft. FM - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES, Finish342.8 ft. AMH - Downstream Manhole, Survey Ends - 18 0669

Observation photos (4)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    28.9 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    49.9 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    177.6 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES, Start

    248.4 ft. - Fracture Multiple, from 08 to 12 o'clock, within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
225.1TF
49.9CL
49.9FL
220.2TFC
177.6FL
123.3TF
322.1TF
0MGOCONNECTION AT MH 9 O'CLOCK
0AMH18 0670
155.5FL
0MWM
248.3FL
28.9CL
248.4FM
118.1TFC
0MGOHEAVY STEAM FROM MH
0MWL
316.9TFC
338.9FM
342.8AMH18 0669

Properties (4)

additional_info
SC365452
custom_field_two
2
customer
LACSD
datetime
2018-11-14T22:34:04-08:00