Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 15, 2018, 07:05 AM
  • 18 0669_18 0668 _14112018_230524.mp4

Date
11/14/2018
W/O
734990
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00696
PipeID
P14518
Time
11:05 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6224
Sewer Name
18 PHOEBE AVENUE TRUNK
City
LA MIRADA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734990_TV18081_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
18 0669
Downstream MH
18 0668
Dir. of Survey
Downstream
Length Surveyed
350.7 ft.
Total Length
350.7 ft.
Structural Index
3
Structural Quick
4D3C
Structural Rating
190
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole 18 0669 to 18 0668
MH: 18 0669MH: 18 0668downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 06690 ft. MWM - Water Mark, 20 %of cross sectional area22.8 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start41.9 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"53.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish53.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start95.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"144 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish144.1 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start162.7 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Finish190.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start197.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"220.6 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish220.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start300 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"305.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"347.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish350.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0668

Observation photos (6)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    22.8 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

    41.9 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    53.1 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

    144.1 ft. - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    190.6 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    220.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (21)

DistanceCodeObservation
300TFC
220.6CL
53.1CL
347.5FM
0MWL
0AMH18 0669
101.2TF
144.1FL
41.9TB
53.1FL
220.6FM
144FL
95.8TF
22.8CL
305.2TFC
190.6CL
197.4TFC
202.9TFC
162.7FL
350.7AMH18 0668
0MWM

Properties (4)

additional_info
SC365452
custom_field_two
2
customer
LACSD
datetime
2018-11-14T23:05:16-08:00