Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2018, 05:37 AM
  • 02 0111_02 0110 _13112018_213711.mp4

Date
11/13/2018
W/O
734861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00237
PipeID
P02278
Time
9:37 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6219
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
36
Purpose
Routine Assessment
Project
RFIR_WO_734861_TV02350_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0111
Downstream MH
02 0110
Dir. of Survey
Downstream
Length Surveyed
312.1 ft.
Total Length
312.1 ft.
Structural Index
3
Structural Quick
463H
Structural Rating
159
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
159
Pipe schematic from manhole 02 0111 to 02 0110
MH: 02 0111MH: 02 0110downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 01110 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 10 %of cross sectional area3.9 ft. FM - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES6.2 ft. CM - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES21.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start53.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES76.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"82.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.5 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES101.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish103.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"125.9 ft. FM - Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES127 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"153.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.4 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES174.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start202.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES204.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"227.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"230.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"251.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"280.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"299.8 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES311.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.5 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK312.1 ft. AMH - Downstream Manhole, Survey Ends - 02 0110

Observation photos (10)

  • Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

    3.9 ft. - Fracture Multiple, from 07 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    6.2 ft. - Crack Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    75.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    101.5 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES

    125.9 ft. - Fracture Multiple, from 09 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    172.4 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    175.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    202.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

    299.8 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES

Observations (29)

DistanceCodeObservation
0AMH02 0111
125.9FM
103.2TF
75.1FM
101.5FM
0MWL
202.1FM
76.9TF
175.9CM
280.9TFC
299.8FM
311.4CM
174.8TF
227.9TF
127TF
312.1AMH02 0110
230.7TF
6.2CM
0MWM
101.5CM
53.1TF
204.3TF
21.7CM
251.4TF
172.4CM
82.8TF
3.9FM
311.5MGOCONNECTION AT MH 9 O'CLOCK
153.7TF

Properties (4)

additional_info
SC365247
custom_field_two
2
customer
LACSD
datetime
2018-11-13T21:37:07-08:00