Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 14, 2018, 06:08 AM
  • 02 0110_02 0109 _13112018_220824.mp4

Date
11/13/2018
W/O
734861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00237
PipeID
P02277
Time
10:08 PM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K6219
Sewer Name
02 BELLFLOWER TRUNK
City
BELLFLOWER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
38
Purpose
Routine Assessment
Project
RFIR_WO_734861_TV02350_NOV2018
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
02 0110
Downstream MH
02 0109
Dir. of Survey
Downstream
Length Surveyed
338.6 ft.
Total Length
338.6 ft.
Structural Index
3
Structural Quick
433L
Structural Rating
204
O&M Index
3
O&M Quick
3B21
O&M Rating
47
Overall Index
3
Overall Quick
Overall Rating
251
Pipe schematic from manhole 02 0110 to 02 0109
MH: 02 0110MH: 02 0109downstream0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 01100 ft. MWM - Water Mark, 25 %of cross sectional area11.5 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES20.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start76.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"100 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"150.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"176.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"203.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"223.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"243.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"267.2 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start270.8 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OFFSET281.3 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES282.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.5 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES296.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES338.6 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Finish338.6 ft. AMH - Downstream Manhole, Survey Ends - 02 0109338.6 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK338.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (6)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    11.5 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    20.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Settled Other,  20 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: YES, Start

    267.2 ft. - Deposits Settled Other, 20 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES

    281.3 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    292.5 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    333.1 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (28)

DistanceCodeObservation
0MGOCONNECTION AT MH 9 O'CLOCK
338.6DSZ
338.6AMH02 0109
243.7TFC
229.4TFC
338.6MGOCONNECTION AT MH 3 O'CLOCK
267.2DSZ
126.6TFC
282.5TF
176.8TF
296.2TF
333.1FM
20.9CM
292.5FM
91.1TF
0MWL
11.5FM
188.4TFC
0AMH02 0110
338.6CM
150.1TFC
100TF
76.6TF
0MWM
281.3DAGS
223.7TF
203.2TFC
270.8TFDOFFSET

Properties (4)

additional_info
SC365247
custom_field_two
2
customer
LACSD
datetime