Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 18, 2017, 12:40 AM
  • 01 0430_01 0429_030817_042322.mp4

Date
02/17/2017
W/O
624309
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00208
PipeID
P00911
Time
4:40 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
4315
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
WO_624309_TV01032_MAR2017
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0430
Downstream MH
01 0429
Dir. of Survey
Downstream
Length Surveyed
303.8 ft.
Total Length
303.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
120
Overall Index
2
Overall Quick
Overall Rating
120
Pipe schematic from manhole 01 0430 to 01 0429
MH: 01 0430MH: 01 0429downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04303.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start82 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"82 ft. MGO - General Observation - PIPE LINED87.8 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"211.3 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"219.4 ft. TF - Tap Factory Made, at 03 o'clock, -, within 8 inches of joint: NO, 4"241.3 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: NO, 4"303 ft. MGO - General Observation - CONNECTION AT 3 O CLOCK303.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish303.8 ft. AMH - Downstream Manhole, Survey Ends - 01 0429

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    3.9 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
303MGOCONNECTION AT 3 O CLOCK
0MWL
303.8AMH01 0429
303.3DAGS
0MWM
211.3TF
87.8TF
3.9DAGS
241.3TF
82TF
0AMH01 0430
219.4TF
82MGOPIPE LINED

Properties (6)

additional_info
SC318730
custom_field_two
4
customer
LACSD
datetime
2017-02-17T16:40:05-08:00
lining
CIPP
year_laid
37179