Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 7, 2017, 11:38 AM
  • 15 1163_15 1162 _01072017_034915.mpg

Date
01/07/2017
W/O
616852
Weather
Light Rain
Operator/Surveyor
R.VARGAS
Sewer ID
Z00635
PipeID
P25909
Time
3:38 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4069
Sewer Name
15 TYLER AVENUE RELIEF TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
23
Purpose
Routine Assessment
Project
WO_616852_DISTRICT15_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Width
24 in.
Upstream MH
15 1163
Downstream MH
15 1162
Dir. of Survey
Downstream
Length Surveyed
254.6 ft.
Total Length
254.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2I11
O&M Rating
101
Overall Index
2
Overall Quick
Overall Rating
101
Pipe schematic from manhole 15 1163 to 15 1162
MH: 15 1163MH: 15 1162downstream0 ft. VC - Vermin Cockroach0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK ACTIVE0 ft. AMH - Upstream Manhole, Survey Begins - 15 11630 ft. MWM - Water Mark, 15 %of cross sectional area2.8 ft. MGO - General Observation - MAGNESIUM H.O. START2.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start99.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"113.1 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"220.3 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 6"251.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish251.7 ft. MGO - General Observation - MAGNEZIUM H.O. FINISH254.6 ft. AMH - Downstream Manhole, Survey Ends - 15 1162

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.8 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0VC
220.3TFA
2.8MGOMAGNESIUM H.O. START
251.7DAGS
0MWL
251.7MGOMAGNEZIUM H.O. FINISH
113.1TFA
99.1TFA
254.6AMH15 1162
0MGOCONNECTION AT MH 9 O'CLOCK ACTIVE
2.8DAGS
0AMH15 1163
0MWM

Properties (7)

additional_info
SC318610
custom_field_two
4
customer
LACSD
datetime
2017-01-07T03:38:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
39519