Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 10, 2017, 09:13 AM
  • 14 1063_14 1062 _10012017_011642.mp4

Date
01/10/2017
W/O
616852
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00585
PipeID
P25989
Time
1:13 AM
Certificate
U-508-7069
System Owner
LACSD
Date Cleaned
01/10/17
Pre-Cleaning
No Pre-Cleaning
Media Label
K4120
Sewer Name
14 10TH STREET WEST TRUNK
City
PALMDALE
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
27
Purpose
Routine Assessment
Project
WO_616852_DISTRICT14_JAN20171
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
14 1062
Downstream MH
14 1063
Dir. of Survey
Upstream
Length Surveyed
450.7 ft.
Total Length
450.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
2
Pipe schematic from manhole 14 1062 to 14 1063
MH: 14 1062MH: 14 1063upstream0 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - 14 106348.7 ft. DSF - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO52.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"450.7 ft. MWL - Water Level, 5 %of cross sectional area450.7 ft. MWM - Water Mark, 5 %of cross sectional area450.7 ft. AMH - Downstream Manhole, Survey Begins - 14 1062450.7 ft. MGO - General Observation - LATERAL AT MH 9 O'CLOCK

Observation photos (1)

  • Deposits Settled Fine,  5 %of cross sectional area, at 06 o'clock,  , within 8 inches of joint: NO

    402 ft. - Deposits Settled Fine, 5 %of cross sectional area, at 06 o'clock, , within 8 inches of joint: NO

Observations (8)

DistanceCodeObservation
0MWL
450.7MGOLATERAL AT MH 9 O'CLOCK
0MWM
0AMH14 1062
0MGOLATERAL AT MH 9 O'CLOCK
402DSF
397.9TF
450.7AMH14 1063

Properties (6)

additional_info
SC306477
custom_field_two
4
customer
LACSD
datetime
2017-01-10T01:13:37-08:00
documentation
PROPIPE
is_lateral_inspection
false