Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 6, 2017, 07:04 AM
  • 05 2629_05 2628 _01052017_231209.mp4

Date
01/05/2017
W/O
616852
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01145
PipeID
P25720
Time
11:04 PM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4051
Sewer Name
05 MANCHESTER AVENUE PUMP RELIEF TRUNK
City
HAWTHORNE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
WO_616852_DISTRICT05_JAN2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2629
Downstream MH
05 2628
Dir. of Survey
Downstream
Length Surveyed
350.3 ft.
Total Length
350.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
140
Overall Index
2
Overall Quick
Overall Rating
140
Pipe schematic from manhole 05 2629 to 05 2628
MH: 05 2629MH: 05 2628downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 26290.1 ft. MWM - Water Mark, 20 %of cross sectional area0.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start348.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.3 ft. AMH - Downstream Manhole, Survey Ends - 05 2628

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    0.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
0.1MWM
350.3AMH05 2628
348.2DAGS
0MWL
0AMH05 2629
0.2DAGS

Properties (6)

additional_info
SC306449
custom_field_two
4
customer
LACSD
datetime
2017-01-05T23:04:21-08:00
documentation
PRO PIPE
is_lateral_inspection
false