Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 12, 2017, 11:09 AM
  • H 1286_H 1285 _01122017_030947.mp4

Date
01/12/2017
W/O
613652
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01183
PipeID
P17302
Time
3:09 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4209
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
11
Purpose
Routine Assessment
Project
WO_613652_TV22154_JAN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1286
Downstream MH
H 1285
Dir. of Survey
Downstream
Length Surveyed
330.6 ft.
Total Length
330.6 ft.
Structural Index
3
Structural Quick
3L2L
Structural Rating
325
O&M Index
2
O&M Quick
2L00
O&M Rating
130
Overall Index
2
Overall Quick
Overall Rating
455
Pipe schematic from manhole H 1286 to H 1285
MH: H 1286MH: H 1285downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - H 12860 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start76.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"84.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"157.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"164.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"221.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.1 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish328.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish328.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish328.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE330.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE330.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK330.6 ft. AMH - Downstream Manhole, Survey Ends - H 1285

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    328.1 ft. - General Observation - COCKROACHES IN MANHOLE

  • General Observation - COCKROACHES IN MANHOLE

    330.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
328.1SSS
0MGOCOCKROACHES IN MANHOLE
164.9TFC
157.5TFC
0MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMHH 1286
328.1DAGS
76.3TFC
328.1SAV
330.6MGOCOCKROACHES IN MANHOLE
2SSS
221.6TFC
328.1MGOCOCKROACHES IN MANHOLE
330.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
330.6AMHH 1285
0MWM
2SAV
2DAGS
0MWL
84.5TFC

Properties (6)

additional_info
SC306711
custom_field_two
3
customer
LACSD
datetime
2017-01-12T03:09:24-08:00
documentation
PRO PIPE
is_lateral_inspection
false