Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Jan 13, 2017, 08:32 AM
  • H 1296_H 1295 _01132017_003331.mp4

Date
01/13/2017
W/O
613652
Weather
Light Rain
Operator/Surveyor
S. LOPEZ
Sewer ID
Z01183
PipeID
P17312
Time
12:32 AM
Certificate
U-111-11880
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K4210
Sewer Name
H JOINT OUTFALL H - UNIT 8L
City
AZUSA
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
12
Purpose
Routine Assessment
Project
WO_613652_TV22154_JAN2017
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
H 1295
Downstream MH
H 1296
Dir. of Survey
Upstream
Length Surveyed
412.4 ft.
Total Length
412.4 ft.
Structural Index
3
Structural Quick
3O2O
Structural Rating
405
O&M Index
2
O&M Quick
2O00
O&M Rating
162
Overall Index
2
Overall Quick
Overall Rating
567
Pipe schematic from manhole H 1295 to H 1296
MH: H 1295MH: H 1296upstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Ends - H 12961.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.6 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish1.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE405.8 ft. MWM - Water Mark, 25 %of cross sectional area405.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start405.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start405.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start412.4 ft. MWL - Water Level, 15 %of cross sectional area412.4 ft. AMH - Downstream Manhole, Survey Begins - H1295

Observation photos (4)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    6.6 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    410.8 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (12)

DistanceCodeObservation
0MWL
6.6MWM
0AMHH1295
6.6SAV
412.4MGOACTIVE CONNECTION AT MH 9 O'CLOCK
6.6DAGS
6.6SSS
410.8SAV
410.8SSS
412.4AMHH 1296
410.8DAGS
410.8MGOCOCKROACHES IN MANHOLE

Properties (6)

additional_info
SC306712
custom_field_two
3
customer
LACSD
datetime
2017-01-13T00:32:23-08:00
documentation
PRO PIPE
is_lateral_inspection
false