Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 7, 2016, 11:26 AM
  • E 0206_E 0205_07112016_032726.mp4

Date
11/07/2016
W/O
597391
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00972
PipeID
P24787
Time
3:26 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3873
Sewer Name
E JOINT OUTFALL E - UNIT 4 RELIEF
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_597391_TV01092_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
21 in.
Upstream MH
E 0206
Downstream MH
E 0205
Dir. of Survey
Downstream
Length Surveyed
463.4 ft.
Total Length
463.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
2
Overall Quick
Overall Rating
4
Pipe schematic from manhole E 0206 to E 0205
MH: E 0206MH: E 0205downstream0 ft. AMH - Upstream Manhole, Survey Begins - E 02060 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - AIR VENT AT MH0 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start460.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish460.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish463.4 ft. AMH - Downstream Manhole, Survey Ends - E 0206

Observation photos (2)

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
0AMHE 0206
460.4DAGS
460.4DAE
2.1DAE
2.1DAGS
0MWM
0MGOAIR VENT AT MH
0MWL
463.4AMHE 0206

Properties (7)

additional_info
SC305203
custom_field_two
4
customer
LACSD
datetime
2016-11-07T03:26:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
37770