Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 1, 2016, 08:53 AM
  • E 0183_E 0182_01112016_015337.mp4

Date
11/01/2016
W/O
597391
Weather
Dry
Operator/Surveyor
R.VARGAS
Sewer ID
Z00972
PipeID
P24764
Time
1:53 AM
Certificate
U-209-211
System Owner
LACSD
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K3869
Sewer Name
E JOINT OUTFALL E - UNIT 4 RELIEF
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_597391_TV01092_OCT2016
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
E 0183
Downstream MH
E 0182
Dir. of Survey
Downstream
Length Surveyed
285.3 ft.
Total Length
285.3 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole E 0183 to E 0182
MH: E 0183MH: E 0182downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - E 01830 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area2.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start109.1 ft. ISSRH - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock149.1 ft. ISSRH - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock282.4 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish282.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish285.2 ft. MGO - General Observation - LATERAL AT MH 9 OCLOCK ACTIVE285.3 ft. AMH - Downstream Manhole, Survey Ends - E 0182

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock,  , within 8 inches of joint: YES, Start

    2.4 ft. - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start

  • Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock

    109.1 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock

  • Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock

    149.1 ft. - Intruding Sealing Ring Hanging, 5 %of cross sectional area, from 08 to 04 o'clock

Observations (12)

DistanceCodeObservation
282.4DAE
285.3AMHE 0182
0MWM
2.4DAGS
109.1ISSRH
285.2MGOLATERAL AT MH 9 OCLOCK ACTIVE
282.4DAGS
0AMHE 0183
2.4DAE
0MGOLATERAL AT MH 9 OCLOCK ACTIVE
149.1ISSRH
0MWL

Properties (7)

additional_info
SC301949
custom_field_two
4
customer
LACSD
datetime
2016-11-01T01:53:07-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
37692