Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 26, 2017, 06:16 AM
  • 16 0086_16 0085 _092617_001027.mpg

Date
09/25/2017
W/O
658240
Weather
Dry
Operator/Surveyor
JUAN B
Sewer ID
Z00639
PipeID
P13100
Time
11:16 PM
Certificate
U-715-07000770
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K4983
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARINO
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
WO_658240_TV16088_SEP2017
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
16 0086
Downstream MH
16 0085
Dir. of Survey
Downstream
Length Surveyed
419.5 ft.
Total Length
419.5 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2P00
O&M Rating
166
Overall Index
2
Overall Quick
Overall Rating
166
Pipe schematic from manhole 16 0086 to 16 0085
MH: 16 0086MH: 16 0085downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 00864.1 ft. MGO - General Observation - PIPE LINED4.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start419.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish419.5 ft. AMH - Downstream Manhole, Survey Ends - 16 0085

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    4.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
4.1MGOPIPE LINED
4.1DAGS
419.4DAGS
0MWM
419.5AMH16 0085
0MWL
0AMH16 0086

Properties (7)

additional_info
SC345975
custom_field_two
4
customer
LACSD
datetime
2017-09-25T23:16:52-07:00
is_lateral_inspection
false
lining
CIPP
year_laid
39052